Loading [MathJax]/extensions/MathMenu.js
Ground Fault by Restriking Surge of SF6 Gas-Insulated Disconnecting Switching and its Synthetic Tests | IEEE Journals & Magazine | IEEE Xplore

Ground Fault by Restriking Surge of SF6 Gas-Insulated Disconnecting Switching and its Synthetic Tests


Abstract:

During a breaking operation of charging current with a disconnecting switch (DS) in SF6 gas-insulated switchgear (GIS), the occurrence of a fault to ground from the DS co...Show More

Abstract:

During a breaking operation of charging current with a disconnecting switch (DS) in SF6 gas-insulated switchgear (GIS), the occurrence of a fault to ground from the DS contact by a restriking surge was reported to be observed. The flashover voltage in this case, is appreciably lower than the normal withstand voltage to the ground. It has been clarified through high-speed photography with an image converter camera that the flashover is caused by a streamer generated during restriking between the DS contacts. In this respect, with the objective of confirming these phenomena in a simulated power system, two synthetic test circuits were constructed by using 550kV DS's. Verification tests were carried out to confirm the equivalence between these two test circuits. The DS's subjected to test withstood a surge voltage of 2.3pu-the maximum voltage obtained by simulating calculations of various GIS configurations.
Published in: IEEE Transactions on Power Apparatus and Systems ( Volume: PAS-102, Issue: 1, January 1983)
Page(s): 219 - 227
Date of Publication: 26 February 2007
Print ISSN: 0018-9510
References is not available for this document.

Select All
1.
H.L. Rorden, J.D. Dils, S.B. Griscom, J.W. Skooglund and E. Beck, "Investigation of Switching Surges Cauised by 345kV Disconnecting-Switch Operation", IEEE Trans. PAS, vol. 77, pp. 838, 1958.
2.
S.B. Griscom, J.W. Skooglund and A.R. Hileman, "Analytical Studies of Overvoltages Caused by Disconnecting-Switch Operation", IEEE Trans. PAS, vol. 77, pp. 833, 1958.
3.
L.C. Weber, L.C. Elliot and H.M. Smith, "1115kV Bus Switching Surges", IEEE Trans. PAS, vol. 77, pp. 777, 1960.
4.
N. Cuk, K.K. Nishikawara, G.G. McCrone and P.T.B. Adams, "Specification and Application of SF6 Compressed Gas Insulated Switchgear-A Utility's Point of View", IEEE PES, 1979.
5.
N. Itoh, Y. Murayamna, S. Ohyama and S. Takeshita, "Switching Requirements for Disconnecting Switch and Earthing Switch of GIS", IEEE PES, 1981.
6.
S. Narimatsu, K. Yamaguchi, S. Nakano and S. Maruyama, "Interrupting Performance of Capacitive Current by Disconnecting Switch for Gas Insulated Switchgear", IEEE PES, 1981.
Contact IEEE to Subscribe

References