Introduction
Due to the electrical parameter mismatch of the electric multiple units (EMUs) and the traction network, network voltage and current fluctuations, and corresponding over-voltage or over-current traction blockade caused by Low frequency oscillation (LFO) occurred frequently in recent years [1]–[6]. Both the voltage and current of the traction network were modulated by low frequency waves depending on the types and locations of EMUs on line. Frequencies of the LFO in some countries were mainly concentrated in the band between 10% to 30% of the network fundamental frequency [7]. However, in China, a lower frequency band was found between 3 to 7 Hz, which was around 6% to 14% of the network fundamental frequency [8].
Time-domain analysis [9], pole analysis [4], [6], [10], impedance analysis [11]–[15], have been applied to reveal the mechanism of the LFO in the cascade system. It can be found that the LFO is affected by the network-side and train-side, or the ‘source’-side and ‘load’-side parameters simultaneously. Network-side parameters relate with the capacity of traction substation and the length of the traction network section, which are the representation of the source internal impedance; while the number of running trains, control strategy, topology and control parameters of the Four-Quadrant Converters (4QCs) or the Line-Side Converter (LSC) of certain train are the contribution terms on the train-side impedance. It is impossible for the LFO to occur if the power source is infinite and the source impedance is zero in the ideal assumption. However, the actual power supply cannot be infinite in reality. LFO appears as increasing the number of EMUs connected to the network at the time of operation preparation, i.e., the light load impedance further decreases because of the EMU parallel connection. In another word, the source is relatively ‘weak’ compared to the ‘strong’ load when the LFO appears. From the view of the LSC control strategy of a train, it lacked damping to suppress the disturbance no matter it was the transient current control in the CRH3 or the d-q decoupling control in the CRH5 [16], [17].
In [16], the stability of the cascade system was analyzed by the generalized Nyquist criterion and Bode diagram. Furthermore, system stability estimation based on the coupling impedance of the cascade system was proposed. However, both the analysis and the estimation only considered the internal current control loop. It is not accurate compared to the closed loop analysis considering the outer voltage loop as well. For the CRH5 EMU, an analytical impedance model of the cascade system in the synchronous d-q frame was proposed, which revealed that the Proportional-Integral (PI) controller of the voltage loop control introduced negative damping to the d-d channel impedance of the LSC in the low frequency range [17]. However, the proposed virtual impedance control would affect the dynamic performance of the LSC in the operation state, or high-power state. Similarly, methods of changing the control parameter or strategy, such as adjusting the PI parameter of LSC controller [18], adopting a multivariable control method [19] for the LSC, might not be adaptive to all states, even though they can improve the stability of the cascade system to suppress the LFO at the low-power stage. In [20], [21], Active Disturbance Rejection Controller (ADRC) has been applied in the LSC, the linear PI controller has been changed to non-linear controller, where the parameters change with the feedback error. ADRC is an adaptive controller, it overcomes the contradiction between the overshoot and rapidity of the traditional PI controller, and improves the ability of the controller to suppress large-scale disturbance. However, it is difficult to perform the parameter setting and system stability analysis for this non-linear controller. Another adaptive control strategy of the LSC has been studied to suppress LFO, i.e., a direct power control based on Model Prediction Control (MPC) [22]. In the d-q decoupled system, active power and reactive power predictive control were introduced in the outer voltage loop of the LSC. This method directly controls the predictions of active and reactive power without the need of inner current loop control. However, the DC voltage overshoot was large in the starting stage, and there were high-order harmonics presented in the united simulation of the ETNCS. At the same time, it also lacked the stability analysis of system by using this non-linear control. LFO can also be suppressed by injecting the current with the same oscillation frequency and opposite phase into the system or compensating the oscillation reactive power through Active Power Filter (APF), Static Synchronous Compensator (STATCOM) or Static Var Generator (SVG) [23]–[25]. However, there is the need of the equipment installation at the network high-voltage side, which is expensive.
In conclusion, to suppress the LFO of the cascade system, it is essentially to increase the system damping. It is easier, however very limited, to increase the system damping through changing the control parameters or strategy of the LSC. Furthermore, there is a tradeoff between the adaptability and the practicality to change the control parameters or strategy. Adaptability reflects in two aspects: the LSC control considers both the low-power start-up and high-power operation states; the LSC control adapts different application scenario, such as different types of trains with different controls. Finally, it can even bring additional voltage fluctuation with other frequencies into the system with the improper control parameter setting. For the method of installing additional reactive power compensation device at the network high-voltage side, it is expensive and might also lead to new instability issue if the device is parallel connected with EMUs due to the shortage of inertia in power electronic devices. Therefore, there is still the need to explore one adaptive method to improve the stability and reliability of the cascade system.
When the LFO occurs, not only does the network voltage and current oscillate, but also the DC side voltage of the LSC fluctuates accordingly, which is due to the tracking performance of the LSC control. Therefore, this paper proposes a LFO suppressing method by suppressing the LSC DC side oscillation based on the on-board energy storage (ES) device. Compared to the method of centralized compensation of system overall reactive power, the distributed on-board ES just needs to suppress the DC-link fluctuation of certain motion unit itself, and its capacity is small. Aiming at the system problem of low damping, the virtual DC machine (VDCM) control strategy for the double directional DC-DC converter is proposed. VDCM control simulates the inertia and damping of DC machine and has good steady-state and dynamic performance, which can keep the DC-link voltage stable and further balance the power transport of the LSC. Furthermore, the on-board ES can also be used to store and then regenerate the braking energy of the train. The on-board supercapacitor ES system has been used in China subway train for regenerating the braking energy [26], however, the application of the on-board ES for the EMU train relatively falls behind due to high power and capacity requirement of the ES. China National key Research & Development plan is carrying out the development of high power and density ES power supply on board for hybrid-drive EMUs to provide short-term power by using the regenerated braking energy through ES [27]. The ES capacity requirement to suppress the LFO is much smaller compared to the one for regenerating the energy. Therefore, the proposed on-board ES method for suppressing the LFO is practical and this function can be combined with the energy regeneration function in the later stage.
The rest of this paper is organized as follows. In Section II, the equivalent mathematical model of ETNCS is established by taking the CRH3 as an example. Based on the Middlebrook impedance ratio criterion, the stability of ETNCS is analyzed, and the critical condition for LFO of EMUs is obtained. The LFO suppression strategy based on on-board energy storage is proposed in Section III. The feasibility of the proposed method is verified by the parameter design of the ES device, the modeling and stability analysis of the DC-DC converter control strategy. In Section IV, the ETNCS simulations validate that the proposed control strategy has LFO suppression capability with better steady-state and dynamic performance compared to PI control. Section V draws conclusion for this work.
Stability Mechanism Analysis of (EMUs)-Traction Network Cascade System
A. Modeling and Analysis of Cascade System Considering Impedance Matching
Fig. 1 shows the structure diagram of EMU-traction network cascade system (ETNCS), including the traction power supply and one EMU.
The system topology is shown in Fig. 2, where all the parameters are converted to the secondary side of the on-board transformer. The output voltage of the substation transformer \begin{align*} Z_{\textrm {os}}=&(Z_{\textrm {s}} +Z_{\textrm {eq}})\parallel Z_{\textrm {C}_{\textrm {f}}} \\=&(R_{\textrm {l}} +sL_{\textrm {l}})\parallel (s^{2}L_{\textrm {l}} C_{\textrm {f}} +sR_{\textrm {l}} C_{\textrm {f}} +1)\tag{1}\end{align*}
A two-unit topology is shown in Fig. 2 with two H-bridge converter connected in parallel, representing one inverter and four motors. The equivalent resistor
A double closed-loop transient current control strategy is used in the CRH3 LSC, as presented in Fig. 3. It is noted that the current reference
Accordingly, the equivalent impedance of the LSC is obtained as follows, \begin{align*} \hspace {-.3pc}Z_{\textrm {in}} (s)=&\frac {s^{2}L_{\textrm {n}} (T_{\textrm {v}} s+1)(0.5T_{\textrm {v}} s+1)(0.5T_{\textrm {d}} s+1)}{s(0.5T_{\textrm {v}} s+1)\left [{ {(T_{\textrm {v}} s+1)(0.5T_{\textrm {d}} s+1)-K_{\textrm {pwm}}} }\right]} \\&+\,\frac {K_{\textrm {pwm}} K_{\textrm {ip}} \left [{ {(K_{\textrm {up}} s+K_{\textrm {ui}})S_{\textrm {ab}} G_{7} +s(0.5T_{\textrm {v}} s+1)} }\right]}{s(0.5T_{\textrm {v}} s+1)\left [{ {(T_{\textrm {v}} s+1)(0.5T_{\textrm {d}} s+1)-K_{\textrm {pwm}}} }\right]} \\\tag{2}\end{align*}
The simplified expression is as follows, \begin{equation*} Z_{\textrm {in}} (s)=\frac {U_{\textrm {s}}}{I_{\textrm {s}}}=\frac {1+G_{3} G_{4} G_{5} (G_{1} G_{2} G_{6} G_{7} +G_{2})}{G_{5} (1-G_{2} G_{4})}\tag{3}\end{equation*}
B. Analysis of Impedance Ratio Criterion
The stability of the ETNCS can be analyzed by using the impedance analysis method for a cascade system [29], [30]. The simplified impedance equivalent model of the ETNCS is shown in Fig. 4.
Then, the traction network voltage is expressed as \begin{equation*} U_{\textrm {s}} (s)=U_{\textrm {o}} (s)\frac {Z_{\textrm {in}} (s)/4}{Z_{\textrm {in}} (s)/4+Z_{\textrm {os}} (s)}=U_{\textrm {o}} (s)\frac {1}{1+T_{\textrm {M}} (s)}\tag{4}\end{equation*}
With the increase of the number of trains, the equivalent impedance of trains decreases, and
Suppose the transformer turns ratio is \begin{equation*} Z_{\textrm {in}} '=\frac {k^{2}Z_{\textrm {in}} (s)}{4n}\tag{5}\end{equation*}
Substituting (3) into (5), the impedance ratio of the ETNCS can be written as, \begin{align*} T_{\textrm {M}} =\frac {Z_{\textrm {os}} (s)}{Z_{\textrm {in}} '}=Z_{\textrm {os}} (s)\frac {4nG_{5} (1-G_{2} G_{4})}{k^{2}(1+G_{3} G_{4} G_{5} (G_{1} G_{2} G_{6} G_{7} +G_{2}))} \\\tag{6}\end{align*}
C. Stability Analysis
According to the field test data of LFO in reference [1]–[3], the actual location of LFO, the length of adjacent traction substation, transmission line and the device parameters of LSC are extracted. The parameter of (6) for CRH3 ETNCS is shown in Table 1 for calculating the impedance ratio
The Bode diagram of the
Fig.6 shows the Matlab/Simulink simulation model of the ETNCS, which is used to reproduce the LFO. Network electrical and LSC control parameters are listed in Table 1. The chain network model has been used to simulate network multi-conductor transmission lines, which is an accurate traction network model [16]. In this study, the traction network is equivalent to a resistor and an inductor by Thevenin’s theorem to facilitate the analysis as some other LFO analysis models [16], [22].
The Bode diagram analysis shows that the critical condition to occur LFO for the CRH3 is that 6 EMUs raise the pantograph at the same time. Therefore, 5 and 6 EMUs are connected to the traction network respectively in the simulation to show the difference of the voltage and current waveforms at both sides of the train and the network. Fig. 7(a) and (b) show that when 5 EMUs are connected to the traction network at the same time, the electrical quantities at both sides of the train and the network will start to oscillate. After 0.2 s, the oscillations will disappear and the system will return to a stable state. When 6 EMUs are raising the pantograph at the same time, the electrical quantities at both sides of the train and the network will continue to oscillate at a low frequency during all the time. Furthermore, it can be seen that LFO occurs synchronously at all links including the transformer inputs (network voltage and current), the AC inputs and DC outputs of the LSC when 6 EMUs are preparing, which are shown in Fig.7 (c) and (d).
The harmonic spectrum in Fig. 8 (a) shows that the magnitude of harmonic component of the network voltage is very low when the train is running stably. The harmonic spectrum in Fig. 8 (b) shows that the frequencies of the inter harmonics of the network voltage are symmetrically distributed on both sides of the fundamental frequency, which are 44Hz and 56Hz respectively. It indicates that the amplitude of the fundamental wave is modulated by the 6Hz low frequency wave. In addition, there is a 6Hz low-frequency component in the network voltage. The simulation results are consistent with the critical conditions of LFO obtained by theoretical analysis. At the same time, the simulation waveform are close to the measured waveforms in reference [16], which verifies the reliability of the model established in this paper.
Control Strategy of Low Frequency Oscillation Suppression Based on On-Board Energy Storage Device
Traditional control methods can be summarized as the impedance match by changing the control parameters or strategy. However, it is difficult to consider both the steady state and dynamic performance of the EMUs. The ES system can compensate the energy exchange during the disturbance stage through certain control strategy, suppressing the power fluctuation and the caused LFO. However, some ES devices such as the battery are not quick enough for compensating a disturbance with quick change [31]. Super-capacitor (SC) has the advantages of long service life, high power density and high charge discharge efficiency. Therefore, SC is chosen as the ES device.
When the LFO occurs, the DC-link voltage and current in the control loop will also show the LFO. The DC voltage and current waveforms and the corresponding power fluctuation in the simulation when the LFO occurs are shown in Fig. 9 and Fig. 10. It can be seen that the DC side power fluctuates in the similar frequency of around 6 Hz as the line side of LSC, and the power peak is 1210 W.
From Fig. 3, it can be seen that the DC voltage is the feed-back in the voltage loop of the LSC, so the DC voltage disturbance directly affects the stability of the system. Therefore, it is effective to improve the stability of the DC-link voltage to suppress the LFO. As shown in Fig. 11, the ES device is now connected with the DC link of the LSC. The ES device will provide a discharging power to compensate the power fluctuation.
The DC-side voltage and power of the LSC respectively are 3000 V and 9000 W during the pantograph lifting preparation. The SC is connected with the DC link through a buck-boost bidirectional DC-DC converter. In order to make the output voltage of the ES converter reach 3000 V quickly, the SC should be charged and discharged continuously. According to the power conservation, the steady value of the discharge current of the SC is 22.5 A; and it should fluctuates around 22.5 A reversely with the DC-link fluctuation.
The capacity of the SC is designed according to the maximum duration of the LFO, which was around 120 s [1], [2]. Therefore, the SC with the total capacity of only 0.75
Fig. 12 is the topological diagram of the EMU connecting with the ES converter. The VDCM is an effective control method of the bidirectional DC-DC to keep the DC link voltage stable compared to other methods [33]. The traditional double closed-loop control based on PI and droop control [34]–[37] lacks inertia and damping, which makes it limited to keep the stability of the DC-link voltage. Here the VDCM control is used to control the on-board ES converter to verify its function of keeping the DC-link voltage stable through the inertia and damping control; and the ES could provide the suppression energy needed by the control.
A. Working Principle and Model Derivation of Energy Storage Converter
In order to avoid frequent charge and discharge of the ES, voltage hysteresis control is applied to determine whether the ES works or not.
As shown in Fig. 13, when DC voltage variation
The LFO causes the oscillation of the output power
When the ES controller detects that the actual value of DC-link side voltage is higher than the upper limit threshold
B. Analysis of Virtual DC Machine
Based on the characteristics of DC machine, the VDCM model of ES converter is shown in Fig. 16. The equivalent two port network of the ES interface converter simulates the inertia and damping characteristics of the DC machine.
The VDCM model can be described by the mechanical rotation equation of the DC machine and the potential balance equation of armature circuit, written as, \begin{align*} \begin{cases} \displaystyle J\frac {d\omega }{dt}=T_{\textrm {m}} -T_{\textrm {e}} -D(\omega -\omega _{0}) \\ \displaystyle T_{\textrm {e}} =\frac {P_{\textrm {e}}}{\omega } \end{cases}\tag{7}\end{align*}
The balance equation of electromotive force is as followed, \begin{align*} \begin{cases} \displaystyle U_{\textrm {dc}} =E-R_{\textrm {a}} I_{\textrm {a}} \\ \displaystyle E=C_{\textrm {T}} \Phi \omega \end{cases}\tag{8}\end{align*}
C. Small Signal Analysis and Parameters
The ES converter adopts traditional double closed-loop constant voltage control, and the block diagram is shown in Fig. 17. The stability of DC voltage can be maintained by adjusting the outer DC voltage loop and the inner current loop, where,
On the basis of above traditional control, the VDCM is realized, which is shown in Fig. 18. Where,
Fig. 18 shows that when the DC side load has power fluctuation, the ES converter adjusts the actual angular velocity
Combine (7) and (8), let \begin{equation*} J\Delta \dot {\omega } =T_{\textrm {m}} -\frac {C_{\textrm {T}}^{2} \Phi ^{2}\omega _{0}}{R_{\textrm {a}}}-\frac {C_{\textrm {T}}^{2} \Phi ^{2}\Delta \omega }{R_{\textrm {a}}}-D\Delta \omega\tag{9}\end{equation*}
Add disturbance to (9), it follows that, \begin{align*}&\hspace {-1pc}J(\Delta \dot {\omega } +\Delta \hat {\omega })=(T_{\textrm {m}} +\mathop {T_{\textrm {m}}}\limits ^{\wedge })-\frac {C_{\textrm {T}}^{2} \Phi ^{2}\omega _{0}}{R_{\textrm {a}}} \\&\qquad \qquad \qquad \quad -\,\frac {C_{\textrm {T}}^{2} \Phi ^{2}(\Delta \omega +\Delta \hat {\omega })}{R_{\textrm {a}}}-D(\Delta \omega +\Delta \hat {\omega }) \\\tag{10}\end{align*}
Separate the disturbance and make variable substitution, so that, \begin{equation*} J\Delta \dot {\omega } =T_{\textrm {m}} -\frac {C_{\textrm {T}}^{2} \Phi ^{2}\Delta \omega }{R_{\textrm {a}}}-D\Delta \omega\tag{11}\end{equation*}
By performing the Laplace transform of (11), the transfer function of the JD module in the VDCM module is obtained, \begin{equation*} G_{\textrm {JD}} (s)=\frac {R_{\textrm {a}}}{JR_{\textrm {a}} s+(C_{\textrm {T}} \Phi)^{2}+DR_{\textrm {a}}}\tag{12}\end{equation*}
Eq. (12) shows that JD module is approximately a first-order inertial link with an ES element, where the rotational inertia \begin{equation*} CU_{\textrm {dc}} \frac {dU_{\textrm {dc}}}{dt}=P_{\textrm {load}} -P_{\textrm {o}}\tag{13}\end{equation*}
Therefore, the voltage fluctuation caused by unbalanced power is mainly related to the DC side capacitance. The larger the capacitance value, the greater the system inertia. However, in the actual DC converter system, the capacitance value is small, which is only 3 mF here; the link voltage is still vulnerable to disturbance.
According to (8), the \begin{equation*} U_{\textrm {dc}} =C_{\textrm {T}} \Phi \omega -I_{\textrm {a}} R_{\textrm {a}}\tag{14}\end{equation*}
Do the angular frequency deviation on both side of (14), the change rate of voltage with angular frequency is obtained, \begin{equation*} \frac {\partial U_{\textrm {dc}}}{\partial \omega }=C_{\textrm {T}} \Phi\tag{15}\end{equation*}
Derived from Fig. 18, the small signal model of the VDCM module is shown in Fig. 19.
The transfer function between the output voltage deviation \begin{align*} G_{\textrm {VDCM}} (s)=&\frac {\Delta E(s)}{\Delta U_{\textrm {dc}} (s)} \\=&\frac {U_{\textrm {ref}} C_{\textrm {T}} \Phi R_{\textrm {a}} (k_{\mathrm {up\_{}vdcm}} s+k_{\mathrm {ui\_{}vdcm}})}{JR_{\textrm {a}} \omega _{0} s^{2}+(C_{\textrm {T}}^{2}\Phi ^{2}\omega _{0} +DR_{\textrm {a}} \omega _{0})s}\tag{16}\end{align*}
The control parameters should be designed according to the dynamic response of the ES device to suppress the LFO. Fig. 20 shows the root locus chart of the VDCM transfer function. Within a certain value range, the increase of \begin{equation*} D=\frac {\Delta T}{\Delta \omega }=\frac {\Delta P_{\textrm {set}}}{2\pi f_{\textrm {n}} \cdot 2\pi \Delta f}\tag{17}\end{equation*}
The power
The value of inertia \begin{equation*} J=\tau _{\textrm {f}} \cdot D\tag{18}\end{equation*}
When
D. Stability Analysis Integrated With Energy Storage
When the ES converter and the LSC work together, according to the proposed control strategy, the ES converter is used to suppress the DC voltage fluctuation, and the DC voltage signal is fed back to the voltage loop of the LSC to suppress the LFO. The control block diagram is shown in Fig. 21.
After further transforming, the transfer function of the equivalent input impedance of the LSC after adding the ES converter can be obtained from Fig. 22, which is shown in (19), \begin{align*} Z_{\textrm {in}} '(s)=&\frac {U_{\textrm {s}}}{I_{\textrm {s}}}=\frac {1+G_{3} G_{4} G_{5} (G_{1} G_{2} G_{6} G_{7} G_{8} +G_{2})}{G_{5} (1-G_{2} G_{4})}\qquad \tag{19}\\ T_{\textrm {M}}=&\frac {Z_{\textrm {os}} (s)}{Z_{\textrm {in}} '} \\=&Z_{\textrm {os}} (s)\frac {4nG_{5} (1-G_{2} G_{4})}{k^{2}(1+G_{3} G_{4} G_{5} (G_{1} G_{2} G_{6} G_{7} \textrm {G}_{8} +G_{2}))} \\{}\tag{20}\end{align*}
Therefore, the impedance ratio between the system output impedance and the input impedance of the train is changed to (20) after considering the ES converter. Fig. 23 shows the impedance ratio Bode diagram of the ETNCS under different conditions when 6 trains are lifting the pantographs at the same time. The low-frequency instability point of Bode magnitude diagram decreases from 0 dB to the below of 0 dB. Compared with before compensation, the bandwidth is also increased and the system stability is enhanced.
Bode diagram of the impedance ratio of ETNCS after adding on-board energy storage device.
E. Comparison of Virtual DC Machine and PI Control
Traditional DC-DC control of the ES converter includes the voltage and current double closed-loop PI control and PWM complementary control to realize the bidirectional power regulation [38]. The parameters of the PI and VDCM controller are shown in Table 3. Fig. 24 shows the Bode diagram comparison when the ES converter adopts the VDCM control and the traditional PI control.
Fig.24 shows that when six trains lift the pantographs, the on-board ES based on PI control can make the low-frequency instability point move down to −1.3 dB, which means the system recovers to the stable state after adding the ES device. However, the peak value of the instability point with the VDCM control is reduced to −17.7 dB. What’s more, the gain margin of PI control is 22.6 dB, and the gain margin of VDCM is 32.5 dB. The VDCM control strategy can further compensate the damping of the ETNCS by introducing the damping coefficient
The DC-link voltage dynamic responses based on these two control methods are compared in Fig. 25. Their performance values are given in Table 4.
It can be seen from Fig. 25 and Table 4 that the voltage overshoot with the ES converter based on the traditional PI control is 24.3%, and the one based on the VDCM control is only 7.3%; the regulation time based on the VDCM control is 0.15 s, which is faster than the 0.45 s dynamic response speed with the PI control; when there is a disturbance, the voltage fluctuation under PI control is larger, however the VDCM control is less affected. Therefore, the dynamic performance of VDCM control is better than traditional PI control, which can make the system reach the steady state quickly and smoothly.
Simulation Verification
The ETNCS with the on-board ES has been simulated again by using above Matlab/Simulink model shown in Fig.6. Parameters in Table 3 have been used in the PI and VDCM controls of the ES converter.
When 6 or 7 EMUs lifting pantographs at the same time with the light load, the ES device is put into operation at 0.5 s in the simulation. Waveforms of the AC inputs and the DC voltage output of the LSC are shown in Fig. 26.
Waveforms of electrical quantity of the ETNCS based on on-board energy storage device.
Fig. 26 shows that the DC-link voltage reaches a stable state within 0.25 s after the ES device is put into operation, and there are no obvious low frequency harmonic components anymore caused by the LFO even when 7 EMUs are raising the pantographs at the same time, which can be seen in Fig.27.
Spectra of the network voltages of ETNCS based on on-board energy storage device.
Fig. 28 shows the DC-link voltage waveforms when the ES converter adopts traditional PI and VDCM control strategies. When the ES device is connected to the DC side of LSC at 0.5 s, the voltage controlled by PI method drops to 2429 V and that controlled by VDCM method is 2767 V. Compared with the traditional PI control, the proposed VDCM control strategy can provide greater damping and appropriate inertia for the system, which makes the DC side voltage dynamic response better and the stability stronger when the ES device is connected to the DC link. It is shown that the ES device based on the VDCM control proposed in this paper can better suppress the LFO of ETNCS.
Fig. 29 shows the Bode diagram of the ETNCS after adding on-board ES devices. The magnitude curve is below 0 dB and the system is stable when 45 trains raise pantographs at the same time. However, the curve peak passes through 0 dB when 46 trains raise the pantographs simultaneously. Therefore, the critical number of trains without showing the LFO after adding on-board ES devices is 45.
Conclusion
In order to suppress the LFO, the DC side power compensation strategy of LSC based on on-board energy storage is proposed. Traditional LFO suppression method of changing the LSC control parameters or strategy is neither adaptive nor practical. The ES device discharges according to the DC voltage deviation. The suppressed DC voltage signal is fed back to voltage loop of the LSC to realize feedback damping compensation. Aiming at the problem that the traditional PI control of the ES converter is not sensitive to power disturbance, a VDCM control strategy is proposed to adaptively respond to DC side power fluctuation and maintain DC voltage stability. The stability criteria and simulation results show that the proposed suppression method makes the ETNCS have greater gain margin, which can accommodate more EMUs. In addition, compared with the traditional PI control, the proposed VDCM control strategy has the advantages of small overshoot, short adjustment time and good dynamic performance.
It should be noted that the proposed control strategy is not limited to a single type EMUs, and it can be extended to other systems by a simple redesign of the ES parameters. Further work in this field can consider the optimization of the energy management strategy of the ES after combining the function of braking energy regeneration. On one hand, it can suppress LFO and improve power quality during the start-up stage; on the other hand, it can be responsible for the regeneration of the braking energy during train deceleration operation. The hybrid ES could also be considered in the future for taking account both the high power and high energy density at the same time.