I. Introduction
Power transformers are known as one of the most important equipment in power system. However, the unavoidable insulation defects in transformers occurring during manufacturing, transportation, assembly, or operation can lead to insulation degradation or even breaking down. The on-site standard lightning impulse (SLI) voltage withstand test is a necessary means to ensure its safe operation. However, due to the large size of conventional impulse voltage generators, SLI voltage withstand tests are rarely performed on site. The oscillating lightning impulse (OLI) voltage is recommended for the field test by IEC60060-3 standard because of its high generation efficiency. The OLI voltage rises rapidly to a peak value and then falls to zero with damped oscillations of a frequency between 15 kHz to 400kHz with or without polarity changes. It is characterized by its front time and time-to-half-value of the enveloping curve and the frequency of the oscillations [1], [2].