IEC 61850-based smart automation system logic to improve reliability indices in distribution networks


Abstract:

This paper proposes an automation system logic for distribution networks with the aims of improving reliability indices through the implementation of selective fault dete...Show More

Abstract:

This paper proposes an automation system logic for distribution networks with the aims of improving reliability indices through the implementation of selective fault detection, fast network reconfiguration ad automatic back-feeding. A hierarchical approach of smart substations is presented base on IEC 61850 standard, electronic instruments, optical fiber communication network, etc. The protection and control system includes three main blocks: primary substation protection, secondary substation protection and the logic selectivity. These three blocks contribute to create the smart automation system which can improve protection performance, in order to transform most of the faults to transitory interruptions lasting less than one second, and control capability of the system. The main issues and challenges of the automation system logic are presented with a detailed description of primary and secondary substations protection system and relays as well as the logic selectivity. Moreover, a case study on a real DN is reported to demonstrate the effectiveness of the proposed approach.
Date of Conference: 18-20 September 2019
Date Added to IEEE Xplore: 07 November 2019
ISBN Information:
Conference Location: Florence, Italy

I. List of Acronym

MS

Secondary substation with manual switch-disconnector and no remote-control apparatus.

RS

Secondary substation with motorized switch-disconnector and remote-control apparatus.

SS

Secondary substation equipped with switch-disconnector and smart relays which allow protection, control and communication with other SSs.

SSH

Secondary substation located halfway from a primary substation and a feeder tie.

SSE

Secondary substation located at the end of a feeder.

SPL

Line protection installed at primary substation level.

SPLL

Line protection installed along a feeder.