In the event of a power system disturbance, it is important that the decision to implement under frequency load shedding is based on both the minimum frequency and the ma...Show MoreMetadata
Abstract:
In the event of a power system disturbance, it is important that the decision to implement under frequency load shedding is based on both the minimum frequency and the magnitude of the disturbance. In this paper, we propose the use of higher order polynomial curve fitting to estimate the minimum frequency. If the prediction shows that the minimum frequency threshold will be violated, the magnitude of the total disturbance is estimated using the swing equation. In addition, the minimum amount of load that must be shed to restore the frequency just above the minimum value can also be directly calculated. Simulations are carried out for the considered Taiwan power system and the results prove the efficiency of the proposed technique.
Published in: 2019 IEEE Milan PowerTech
Date of Conference: 23-27 June 2019
Date Added to IEEE Xplore: 26 August 2019