Abstract:
Shunt active power filters are connected in parallel with the electricity supply network. If the AC mains has a neutral conductor, it is desirable to compensate the mains...Show MoreMetadata
Abstract:
Shunt active power filters are connected in parallel with the electricity supply network. If the AC mains has a neutral conductor, it is desirable to compensate the mains harmonic currents zero-sequence components. This can be achieved with a four-wire pulsewidth modulation voltage converter connected to the AC mains. In this case, the three-phase and the neutral AC currents must be controlled. A generalization of the space-vector-based current controller in the /spl alpha//spl beta/o coordinate system is presented in this paper. With this current controller, all the current harmonic systems of positive, negative, and zero sequence can be injected by the converter and, thus, compensated on the AC mains. The system is also useful to compensate unbalanced currents of fundamental frequency. A useful benefit of this system is that it is possible to control the converter four-wire currents with equal hysteresis errors. Simulation and experimental results are presented.
Published in: IEEE Transactions on Industrial Electronics ( Volume: 45, Issue: 5, October 1998)
DOI: 10.1109/41.720333
References is not available for this document.
Select All
1.
J. Holtz, "Pulsewidth modulationA survey", IEEE Trans. Ind. Electron., vol. 39, pp. 410-420, Dec. 1992.
2.
A. Trzynadlowski, "An overview of modern PWM techniques for three-phase voltage-controlled voltage-source inverters", Conf. Rec. IEEE-ISIE96, pp. 25-39, 1996.
3.
M. P. Kazmierkowski and M. A. Dzieniakowski, "Review of current regulation techniques for three-phase PWM inverters", Conf. Rec. IEEE-IECON9, pp. 567-575, 1994.
4.
M. P. Kazmierkowski and W. Sulkowski, "Novel space vector based current controllers for PWM-inverters", Proc. PESC89, pp. 657-664, 1989.
5.
H. Akagi, "New trends in active power filters", Proc. EPE95, vol. 0, pp. 17-26, 1995.
6.
F.-Z. Peng, H. Akagi and A. Nabae, "A study of active power filters using quad-series voltage-source PWM converters for harmonic compensation", IEEE Trans. Power Electron., vol. 5, pp. 9-15, Jan. 1990.
7.
P. Verdelho and G. Marques, "An active power filter and unbalanced current compensator", IEEE Trans. Ind. Electron., vol. 44, pp. 321-328, June 1997.
8.
P. Verdelho and G. Marques, "An active power filter and unbalanced current compensator control circuit", Proc. EPE95, pp. 1929-1934, 1995.
9.
P. Verdelho, " Space vector based current controller in alphabeta 0 coordinate system for the PWM voltage converter connected to the AC mains ", Proc. PESC97, pp. 1115-1120, 1997.
10.
M. Aredes, K. Heumann and J. Hafner, "A three-phase four-wire shunt active filter employing a conventional three-leg converter", EPE J., vol. 6, no. 3/4, pp. 54-59, Dec. 1996.