Abstract:
Frequency-dependent node-to-node impedance function (NIF) models of power system equipment based on systematic broad frequency range (50 Hz to 1 MHz) external driving poi...Show MoreMetadata
Abstract:
Frequency-dependent node-to-node impedance function (NIF) models of power system equipment based on systematic broad frequency range (50 Hz to 1 MHz) external driving point impedance measurements are described. Such models are needed to calculate and predict the radio frequency electromagnetic (EM) noise produced by the valve ignition of a converter station. The application of the transformer frequency-domain NIF model related to HVDC converter station EM noise calculations is demonstrated. Calculated performance data are compared with field measurements.<>
Published in: IEEE Transactions on Power Delivery ( Volume: 8, Issue: 1, January 1993)