Results of subsynchronous resonance test at Mohave | IEEE Journals & Magazine | IEEE Xplore

Results of subsynchronous resonance test at Mohave


Abstract:

The results of the subsynchronous resonance test conducted on the number 2 turbine-generator at the Southern California Edison Company Mohave Generating Station are prese...Show More

Abstract:

The results of the subsynchronous resonance test conducted on the number 2 turbine-generator at the Southern California Edison Company Mohave Generating Station are presented and discussed. Comparisons are made between measured and calculated torsional natural frequencies and mode shapes, and the damping associated with each torsional mode stimulated is presented at various loads. In addition, the methods of stimulating the mechanical torsionals of the turbine-generator set are discussed along with a description of the instrumention system that was used to obtain the data.
Published in: IEEE Transactions on Power Apparatus and Systems ( Volume: 94, Issue: 5, September 1975)
Page(s): 1878 - 1889
Date of Publication: 27 March 2006
Print ISSN: 0018-9510

Contact IEEE to Subscribe

References

References is not available for this document.