Abstract:
A type test for gas-insulated substation (GIS) disconnectors is discussed. The author introduces the complexities of the topic, provides a summary of the technical backgr...Show MoreMetadata
Abstract:
A type test for gas-insulated substation (GIS) disconnectors is discussed. The author introduces the complexities of the topic, provides a summary of the technical background, poses the questions which must be addressed, and discusses the technical and commercial considerations which influence the approach toward a solution. The purpose is to provide a systematic context in which the problem can be considered and give the interested nonspecialist the background necessary to provide input to the process of standard preparation and to judge the quality of the result. GIS disconnectors typically fail during normal operation, not as a result of an abnormal system stress, and disconnectors are operated frequently. As a result, any type test must assure that the probability of failure per operation is in the range of 0.001%. Three possible approaches to type testing are identified, two of which appear to be realistic alternatives. Analysis of these alternatives results in the conclusion that the required test parameters cannot be defined from first principles. the parameters will probably be based on past experience and defined so that disconnectors which have not been adequately reliable would not pass the type test while those which have been reliable will pass.<>
Published in: IEEE Transactions on Power Delivery ( Volume: 5, Issue: 4, October 1990)
DOI: 10.1109/61.103680
References is not available for this document.
Select All
1.
S. A. Boggs, F. Y. Chu, N. Fujimoto, A. Krenicky, A. Plessl and D. Schlicht, "Disconnect Switch Induced Transients and Trapped Charge in Gas-Insulated Substations", IEEE Trans on Power Apparatus and Systems, vol. PAS-101, no. 10, Oct. 1982.
2.
S. A. Boggs, N. Fujimoto, M. Collod and E. Thuries, "The Modeling of Statistical Operating Parameters and the Computation of Operation-Induced Surge Waveforms for GIS Disconnectors", 1984 CIGRE.
3.
N. Wiegart, L. Niemeyer, F. Pinnekamp, W. Boeck, J. Kindersberger, M. Morrow, et al., "Inhomogeneous Field Breakdown in GIS - The Prediction of Breakdown Probabilities and Voltages Part I: Overview of a Theory for Inhomogeneous Field Breakdown in SF6", IEEE Trans. Power Delivery, vol. 3, no. 3, pp. 923, July 1988.
4.
N. Wiegart, L. Niemeyer, F. Pinnekamp, W. Boeck, J. Kindersberger, M. Morrow, et al., "Inhomogeneous Field Breakdown in GIS - The Prediction of Breakdown Probabilities and Voltages Part II: Ion Density and Statistical Time Lag", IEEE Trans. Power Delivery, vol. 3, no. 3, pp. 931, July 1988.
5.
N. Wiegart, L. Niemeyer, F. Pinnekamp, W. Boeck, J. Kindersberger, M. Morrow, et al., "Inhomogeneous Field Breakdown in GIS - The Prediction of Breakdown Probabilities and Voltages Part III: Discharge Development in SF6 and a Computer Model of Breakdown", IEEE Trans. Power Delivery, vol. 3, no. 3, pp. 939, July 1988.
6.
S. Narimatsu, K. Yamaguchi, S. Nakano and S. Maruyama, "Interrupting Performance of Capacitive Current by Disconnecting Switch for Gas Insulated Switchgear", IEEE Trans PAS-100, no. 6, June 1981.
7.
A. Bargigia, G. Mazza, A. Pigini and G. Rizzi, "Strength of Typical GIS Configurations with Special Reference to Composite and Combined Stresses" in Gaseous Dielectrics V, Pergamon, pp. 621, 1987.