Abstract:
This paper presents further improvements to a phase-domain ARMA (auto-regressive moving average) line model that is implemented in the ATP version of EMTP. According to t...Show MoreMetadata
Abstract:
This paper presents further improvements to a phase-domain ARMA (auto-regressive moving average) line model that is implemented in the ATP version of EMTP. According to the improvement to convolution, each ARMA model, which reproduces the phase-domain frequency dependence of a transmission line, uses its own economical time step considering the frequency characteristic. Linear interpolation is used to allow a different time step for each ARMA model, and this new convolution strategy makes transient calculations more efficient. A steady-state initialization method of the line model is developed, and fault-surge calculations requiring the initialization are demonstrated. Convenient stability criteria of the line model are also presented.
Published in: IEEE Transactions on Power Delivery ( Volume: 12, Issue: 3, July 1997)
DOI: 10.1109/61.637011