Field measurements of transformer single-phase exciting current as a diagnostic tool, and influence of load tap changers


Abstract:

The single-phase exciting-current test can be used to detect undesirable conditions in single- and three-phase transformers. Normally the test results are analyzed by com...Show More

First Page of the Article

Abstract:

The single-phase exciting-current test can be used to detect undesirable conditions in single- and three-phase transformers. Normally the test results are analyzed by comparing currents between all three phases in a given transformer and between similar single-phase units. Certain problems, however, can be detected on the basis of current change when the measurements are performed on different load tap changer positions. Accordingly, understanding how the load tap changer affects the current magnitude of individual phases is essential for developing proper analysis. This paper identifies twelve patterns of test result behavior, and an attempt is made to show different load tap changer designs as they affect the measurement. The test results and test circuit diagrams are given. The derived patterns will be implemented in a DOS-based expert system in combination with a data acquisition system which is currently used in the field by more than 80 utilities.<>
Published in: IEEE Transactions on Power Delivery ( Volume: 9, Issue: 3, July 1994)
Page(s): 1466 - 1475
Date of Publication: 06 August 2002

ISSN Information:

First Page of the Article

Citations are not available for this document.

Cites in Papers - |

Cites in Papers - IEEE (2)

Select All
1.
"IEEE Guide for Diagnostic Field Testing of Fluid-Filled Power Transformers, Regulators, and Reactors", IEEE Std C57.152-2013, pp.1-121, 2013.
2.
S. Birlasekaran, S.S. Choi, A.C. Liew, "Overview of diagnostic and condition monitoring techniques for in-service power apparatus", Proceedings of EMPD '98. 1998 International Conference on Energy Management and Power Delivery (Cat. No.98EX137), vol.2, pp.673-678 vol.2, 1998.

Cites in Papers - Other Publishers (2)

1.
Behnam Feizifar, Omer Usta, "A new arc-based model and condition monitoring algorithm for on-load tap-changers", Electric Power Systems Research, vol.167, pp.58, 2019.
2.
A Cardoso, Luís Oliveira, Transformers, pp.287, 2012.
Contact IEEE to Subscribe

References

References is not available for this document.