Abstract:
This note shows that the generalized Popov criterion cannot be used to construct a Lur'e-type Lyapunov function for a multimachine power system model if transfer conducta...Show MoreMetadata
Abstract:
This note shows that the generalized Popov criterion cannot be used to construct a Lur'e-type Lyapunov function for a multimachine power system model if transfer conductances are included. The two-machine case of the above paper is an exception.
Published in: IEEE Transactions on Automatic Control ( Volume: 19, Issue: 5, October 1974)