Abstract:
This paper shows that a well-defined energy function can be developed to reflect the transfer conductances for multi-machine power systems under an assumption that all tr...Show MoreMetadata
Abstract:
This paper shows that a well-defined energy function can be developed to reflect the transfer conductances for multi-machine power systems under an assumption that all transmission lines have uniform R/X ratios. The energy function is derived by introducing a pure reactive equivalent system for the given system. In this study, a static energy function reflecting transfer conductances is also derived as well as the transient energy function. The proposed static energy function is applied to voltage stability analysis and tested for various sample systems. The test results show that the accuracy of voltage stability analysis can be considerably improved by reflecting transfer conductances into the energy function.
Date of Conference: 31 January 1999 - 04 February 1999
Date Added to IEEE Xplore: 06 August 2002
Print ISBN:0-7803-4893-1